Contaminant and Unit of Measurement Dates of sampling (mo./yr.) MCL Violation Y/N Level Detected Range of Results MCLG MCL Likely Source of Contamination
Radiological Contaminants  
Radium 226 (pCi/L) Aug-06 N 0.1 N/A 0 5 Erosion of natural deposits
Contaminant and Unit of Measurement Dates of sampling (mo./yr.) MCL Violation Y/N Level Detected Range of Results MCLG MCL Likely Source of Contamination
Inorganic Contaminants          
Fluoride (ppm) Aug-06 N 0.094 N/A 4 4 Erosion of natural deposits; water additive which promotes strong teeth; discharge from fertilizer and aluminum factories
Sodium (ppm) Aug-06 N 21 N/A N/A 160 Salt water intrusion, leaching from soil
Synthetic Organic Contaminants including Pesticides and Herbicides  
Dalapon (ppb) Mar-06 &    Sep-06 N 1.3 0 - 1.3 200 200 Runoff from herbicide used on rights of way
TTHMs and Stage 1 Disinfectant/Disinfection By-Product (D/DBP) Parameters  
For the following parameters monitored under Stage 1 D/DBP regulations, the level detected is the annual average of the quarterly averages:  Chlorine, Haloacetic Acids, and TTHM (MCL 80 ppb). Range of Results is the range of results (lowest to highest) at the individual sampling sites.
Contaminant and Unit of Measurement Dates of sampling (mo./yr.) MCL Violation Y/N Level Detected Range of Results MCLG or MRDLG MCL or MRDL Likely Source of Contamination
Chlorine (ppm) 1/06-12/06 N 0.8 0.6 - 1.2 MRDLG = 4 MRDL = 4 Water additive used to control microbes
Haloacetic Acids (five) (HAA5) (ppb) 3/06-12/06 Y* 123.9 10.5 - 209.8 NA MCL = 60 By-product of drinking water disinfection
TTHM [Total trihalomethanes] (ppb) 3/06-12/06 Y** 124.8 24.1 - 226.58 NA MCL = 80 By-product of drinking water disinfection